Electrical Inspection Report Template
Electrical inspection report template covering service entrance, panels, GFCI/AFCI, code compliance.
Download — Free, No Signup
View or download the full template. All formats include the same content.
Tip: Open the MD file and paste into Google Docs or Word to format with your brand colors, then export as PDF.
Template Preview
Below is the complete template. Copy any section, or download the full file above.
# Electrical Inspection Report **Property:** _______________________________________ **Inspection Date:** _______________ **Inspector:** _______________ Master License #: _______________ --- ## 1. Service Entrance **Service amperage:** _____ amps (120/240V single-phase typical; 200A standard for modern homes) **Voltage measured:** L1-L2: _____ V | L1-N: _____ V | L2-N: _____ V **Service drop type:** ☐ Overhead (mast/weatherhead) ☐ Underground (lateral) **Meter base condition:** ☐ Good ☐ Rust ☐ Damaged seal ☐ Tampering signs **Service entrance conductors:** Size _____ AWG, Type ☐ Copper ☐ Aluminum **Grounding electrode system:** - ☐ Ground rod(s): qty _____, depth _____ ft (8 ft minimum required, two rods 6 ft apart per NEC 250.53) - ☐ Ufer ground (concrete-encased electrode in foundation) - ☐ Water pipe ground (must have supplemental electrode) - Ground resistance test: _____ ohms (target <25 ohms; <5 preferred) ## 2. Main Service Panel **Brand/model:** _______________________________ **Manufactured year:** _____ **Number of spaces:** _____ total, _____ in use, _____ available **KNOWN PROBLEM PANELS (replace if present):** ☐ Federal Pacific Electric (FPE) Stab-Lok — FIRE HAZARD, well-documented ☐ Zinsco / Sylvania-Zinsco — same fire hazard issue ☐ Pushmatic / Bulldog — obsolete, parts unavailable ☐ Challenger panels — recall history If above present: STRONGLY RECOMMEND PANEL REPLACEMENT (insurance carriers increasingly require) **Panel observations:** ☐ Cover fits properly, no missing knockouts ☐ Bonding screw/strap properly installed (main bonding jumper) ☐ Neutrals and grounds separated correctly: - Service panel: bonded together - Sub-panels: kept SEPARATE per NEC 250.142(B) ☐ No double-taps (two wires under one breaker terminal) — code violation ☐ Adequate working space (NEC 110.26): 30" wide, 36" deep, 78" high clear ☐ Spaces filled with knockouts/blanks (no open knockouts) ☐ Labeling: ☐ All circuits clearly labeled ☐ Some labeling ☐ No labeling ## 3. Branch Circuits ### Required GFCI protection (NEC 210.8) ☐ Kitchen counter outlets (within 6 ft of sink) ☐ Bathroom outlets (all) ☐ Garage outlets (all) ☐ Outdoor outlets ☐ Laundry sink area ☐ Within 6 ft of any sink (most kitchens, bathrooms, wet bars) ☐ Crawlspaces, unfinished basements ☐ Pool/spa areas (separate dedicated circuit) ☐ Dishwasher / disposal (NEC 422.5) ☐ Garbage disposal GFCI test result (sample test of each protected location): ☐ All tested GFCIs trip when test button pressed ☐ Some GFCIs failed to trip (recommend replacement) ### Required AFCI protection (NEC 210.12) Applies to most 120V circuits in dwelling units (bedrooms, living rooms, family rooms, hallways, dining rooms, closets, etc.): ☐ All required AFCI breakers installed ☐ Some AFCI present, others missing ☐ No AFCI protection (older home, code update recommended) **Note:** Adding AFCI to older wiring sometimes causes nuisance tripping due to shared neutrals (multi-wire branch circuits) ### Tamper-resistant receptacles (NEC 406.12) Required in dwelling units (since 2008 code): ☐ All accessible outlets tamper-resistant ☐ Some outlets need replacement ☐ Pre-2008 home — not required to retrofit ## 4. Wiring Method **Visible wiring (basement/attic/crawl):** ☐ Romex (NM cable) — modern standard, post-1965 typical ☐ BX (armored cable) — older but acceptable ☐ Knob & tube — pre-1950, RECOMMEND REPLACEMENT ☐ Aluminum branch circuit wiring (1965-1973) — fire risk, requires AlumiConn or COPALUM correction **Wiring concerns:** ☐ Wire size matches breaker (14 AWG ↔ 15A, 12 AWG ↔ 20A, 10 AWG ↔ 30A) ☐ Conductor insulation intact ☐ Proper junction boxes (no open splices) ☐ Cable supports adequate (every 4.5 ft per NEC 334.30) ☐ Cable protected through studs (1.25" depth or nail plates) ## 5. Outlets & Switches **Sample tested:** | Location | Polarity | Ground | GFCI/AFCI | Notes | |---|---|---|---|---| | | ☐ Correct ☐ Reversed | ☐ Yes ☐ No | ☐ N/A ☐ Tested ☐ Failed | | | | ☐ Correct ☐ Reversed | ☐ Yes ☐ No | ☐ N/A ☐ Tested ☐ Failed | | **Common issues observed:** ☐ Open ground (3-prong outlets but no ground wire) — common in 1960s+ homes with 2-wire systems ☐ Reverse polarity (hot/neutral swapped) ☐ Backstabbed outlets (push-in connections) — recommend replacement with screw-terminal ☐ Old-style ungrounded outlets in newer locations ☐ Loose receptacle in wall box ## 6. Service Panel Heat / Issues ### Infrared thermal imaging (if performed) ☐ No hot spots observed ☐ Hot connection identified: _____ (over 100°F above ambient indicates problem) ☐ Loose connections discovered during torque check ### Connection check ☐ Lugs torqued to manufacturer spec ☐ No visible scorching at terminations ☐ Breakers fit properly (no gaps) ☐ Neutral bar tight ## 7. Generators & Solar (if present) ### Backup generator ☐ Manufacturer/model: _______________ ☐ Fuel type: ☐ Natural gas ☐ Propane ☐ Diesel ☐ Gasoline ☐ Capacity: _____ kW ☐ Transfer switch: ☐ Automatic ☐ Manual ☐ Last service date: _______________ ☐ Test run weekly (automatic if applicable) ### Solar PV system ☐ Solar disconnect labeled and accessible ☐ Backfed breaker meets 120% rule (NEC 705.12) ☐ Production meter installed ☐ DC isolator at array (per NEC 690 rapid shutdown) ☐ Battery storage system (if present) properly fused ## 8. Required Safety Devices ### Smoke detectors (NFPA 72) ☐ One in each bedroom ☐ Outside sleeping areas ☐ One on each story including basement ☐ Interconnected (when one trips, all trip) — required in new construction ☐ Hardwired with battery backup (or 10-year sealed battery acceptable) ☐ Less than 10 years old (manufacture date on back) ### CO detectors ☐ Within 10 ft of every sleeping area ☐ On every level (where fuel-burning appliances or attached garage) ☐ Combination smoke/CO acceptable ### AFCI/GFCI testing (monthly recommended) ☐ Customer demonstrated how to test ☐ Provided written instructions ## 9. Code Violations Found | Violation | NEC Reference | Severity | Suggested Action | |---|---|---|---| | | | ☐ Critical ☐ Major ☐ Minor | | | | | ☐ Critical ☐ Major ☐ Minor | | | | | ☐ Critical ☐ Major ☐ Minor | | ## 10. Repair Recommendations ### Priority 1: Safety / Fire Risk _________________________________________________________________ ### Priority 2: Code Compliance _________________________________________________________________ ### Priority 3: Performance / Convenience _________________________________________________________________ ## 11. Cost Estimates | Item | Estimated Cost | |---|---| | GFCI installation (per outlet) | $_____ | | AFCI breaker upgrade | $_____ each | | Panel replacement (200A) | $_____ - $_____ | | Ground rod installation | $_____ - $_____ | | Outlet replacement (each) | $_____ | | Service upgrade to 200A | $_____ - $_____ | | Generator transfer switch | $_____ - $_____ | **Total estimated range:** $_____ - $_____ ## 12. Inspector Notes _________________________________________________________________ _________________________________________________________________ _________________________________________________________________ ## 13. Signatures **Inspector:** Signature: _______________________________ Date: __________ Master License #: _______________ --- *This inspection identifies visible electrical conditions. Concealed wiring not inspected.* *For comprehensive whole-house electrical assessment, infrared thermal imaging available as add-on.*
What's Included
This electrical inspection report template includes 6 pre-built sections:
- 1. Service Entrance
- 2. Main Panel
- 3. Branch Circuits
- 4. GFCI/AFCI
- 5. Safety Devices
- 6. Code Violations
How to Use This Template
- 1 Download the format you prefer.
Word (.docx) for desktop editing, PDF for printing, Google Docs for cloud collaboration.
- 2 Customize with your business info.
Add your logo, business address, license number, and insurance information.
- 3 Fill in project-specific details.
Each section has placeholders showing what to include. Replace with your actual project info.
- 4 Get signatures and store.
Always get both parties to sign and date. Keep digital and printed copies.
💡 Pro Tip: Graduate to Software
Templates work great for low-volume contractors. Once you're handling 10+ jobs/month, software like ServiceTitan or Jobber will save you 5-10 hours per week by auto-generating proposals from your project data.
See best Electrical software →Frequently Asked Questions
Is this Electrical Inspection Report Template really free?
Yes — completely free, no email signup or paywall. Download in Word, PDF, or Google Docs format.
Can I customize this template?
Absolutely. Open in Word or Google Docs and edit all sections to fit your specific Electrical business.
Is this legally binding once signed?
When properly completed, signed, and dated by both parties, this template creates a binding agreement. For complex or high-value projects, consult an attorney.
What software should I pair with this template?
Most Electrical contractors graduate from templates to software like ServiceTitan when their volume exceeds 10-20 jobs/month.